VRF Renewal

tl_files/Produkty/Renewal/Glowna/Panasonic-Renewal -wymiana urzadzen z czynnikiem R22.jpg

 

Panasonic’s Renewal system allows a completely new VRF system, indoor and outdoor units, to be installed using the existing systems pipe work. Panasonic’s advanced technology enables the system to work with previously installed pipe work by managing the working pressure within the system down to R22 (33 bar) levels, this ensures the system works safely              and efficiently without loss of capacity. The new equipment can offer increased COP/EER by using state of the art inverter compressor and heat exchanger technology.
Having contacted your Panasonic supplier regarding pipe work restrictions and gained approval to use the Panasonic Renewal System there are three main tests that have to be carried out to ensure that the system can be used effectively.

Firstly, a thorough inspection of the pipe work must be carried out and any damage must be repaired. Secondly, an oil test has to be carried out to ensure that the system has not been subject to a compressor burnout during its lifetime. Lastly a VRF Renewal Kit (CZ-SLK2) has to be installed within the pipe work to ensure that the system is cleaned of any remnants of oil.

VRF Renewal Kit (CZ-SLK2) and Sight Glass

The following shows an overview of the VRF Renewal Kit (CZ-SLK2) that is required when existing tubing is reused. If the exact tube length and tube size of the existing tubing are uncertain, attach a sight glass in accordance with the figure below. It will be used for checking the amount of additional refrigerant charge.

 

 

Sight glass (field supply)

If the exact tube length and tube size of the existing tubing are uncertain, attach a sight glass to the liquid tubing, and use it to check whether there is an appropriate amount of additional refrigerant charge.

Attaching the Filter Drier Kit and sight glass

• To adjust the limited pressure level into 3.3 MPa, special settings are necessary at site.
• A filter Drier shall be attached to the liquid tubing of each outdoor unit.
• High-Pressure switches shall be attached to both the liquid and the gas tubings of each outdoor unit.
• There is no need to remove the Filter Drier Kit after a test run as normal operation continues while it is attached.
• When attaching the Filter Drier Kit, care shall be taken with regards to the installation location and orientation of the filter drier and ball valve. If a mistake is made, the refrigerant in the system needs to be recovered when the filter drier is replaced, which will make maintenance difficult.
• Thermal insulation material (field supply: heat resistance of 80ºC or higher and thickness of 10 mm or greater) shall be applied to the Filter Drier Kit.
• The filter drier of the Filter Drier Kit may need to be replaced depending on the condition of the existing unit. Use a Danfoss DMB 164 as the replacement filter drier (field supply).

 

More on www.wymianar22.pl

 

 